Start from the average, not the rated amps
Compressor fridges spend most of the day off. The number printed as rated input current, often 7 to 10 amps, is what the compressor can pull while it is running. Wiring cares about that number. A battery plan does not.
Dometic publishes a second figure, average energy consumption in Ah/h, at a named ambient temperature and a named interior temperature. On the CFX3 45 that is 1.03 Ah/h at 32°C ambient and 4°C inside. Dometic’s own FAQ says to divide usable battery amp-hours by that Ah/h to estimate hours of runtime.
Ah/h times 24 is amp-hours per day. Times 12 volts, because the test is on 12 V, is watt-hours per day. For the CFX3 45 at its test point that is about 25 Ah/day, or just under 300 Wh/day, before you add a light or a fan.
Temperature changes the duty cycle
Heat leaks through the insulation in proportion to the difference between the air outside and the cabinet setpoint. The planner scales the published average by (your ambient − your setpoint) ÷ (the test ambient − the test interior). At the published test point the scale is 1 and you get the datasheet number back.
The scale is held between 0.35 and 2.5. A cold night does not make the compressor disappear, and a setpoint typo should not multiply the datasheet by ten. That clamp is a planning limit. It is not a curve from Dometic or ARB.
ARB’s Zero 47 store page lists current draw as 0.8 Ah, and the Zero product release ties that figure to 41°F inside and 89.6°F outside. ARB does not write “per hour.” The planner says so on the result and still treats 0.8 as average amps, because otherwise the figure cannot become a day.
Usable capacity is not always the label
Battle Born’s BB10012 datasheet lists 100 Ah, 12 V, and 100% usable depth of discharge. Renogy’s Core manual says the 100 Ah battery can be discharged to 100%, and quotes cycle life at 80% DOD. The depth-of-discharge slider starts at the published usable figure. Drag it down if you want a reserve the sheet does not require.
Neither battery prints watt-hours. The plan multiplies published amp-hours by the published nominal voltage: 100 × 12 = 1,200 Wh for the Battle Born, 100 × 12.8 = 1,280 Wh for the Renogy Core.
Power stations are already in watt-hours. EcoFlow’s DELTA 2 manual says 1,024 Wh. That is the pack capacity the plan uses. Dometic’s CFX FAQ describes lead-acid as about half usable and LiFePO4 as nearly all usable. This catalog does not include a lead-acid battery, so that 50% rule is not applied to anyone’s lithium pack.
Days off-grid
Add the other loads as watts times hours. A 6 W light for 4 hours is 24 Wh. Divide usable watt-hours by the daily total for battery-only days. If solar or a DC-DC charger puts energy back, subtract that from the daily load first. When replenishment covers the day, the plan says Covered instead of inventing a huge day count.
Open the calculator with the CFX3 45, the Battle Born, and a 100 W panel already filled in, then change one number at a time. The address bar keeps the plan.